Compare the complete ABB TU835V1 3BSE013236R1 marking, hardware configuration and connections with the installed item before approving a replacement.
-
Check the offered item before ordering
Request clear label and connector photographs of ABB TU835V1 3BSE013236R1. Ask your maintenance team to compare the offered item with the installed equipment and the applicable ABB TU835V1 Data Sheet, article 3BSE013236R1 before ordering.
Technical specifications for TU835V1 3BSE013236R1
-
Manufacturer:ABB
-
Product Category:DCS Systems
-
Spare Part Number:3BSE013236R1
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
I/O channels:8
-
Maximum rated voltage:50 V
-
Maximum current per I/O channel:2 A
-
Maximum process-connection current:8 A
-
Signal and supply terminals:16 channel terminals; 4 process-power and 4 process-power 0 V terminals
-
Compatible I/O modules:AI810, AI815 and AI845; single I/O
-
Mechanical keying:2 keys, 6 positions each; 36 combinations
-
Solid conductor cross-section:0.2–4 mm²
-
Stranded conductor cross-section:0.2–2.5 mm²
-
Terminal tightening torque:0.5–0.6 N·m
-
Operating ambient:0 to +55 °C; approval range +5 to +55 °C
-
Protection and humidity:IP20; 5–95% RH, non-condensing
Information
- ABB TU835V1 3BSE013236R1 organizes analog field wiring into two isolated process-power groups while carrying ModuleBus communication through the station. Mechanical keying keeps the fitted I/O module aligned with the intended terminal arrangement.
Electrical limits: 50 V rated voltage and 2 A per channel
Power grouping: Two individually isolated groups
The termination unit distributes ModuleBus to its fitted I/O module and onward to the next MTU. Position signals are shifted to establish the module address. AI810, AI815 and AI845 are supported in single-I/O arrangements. Two six-position mechanical keys provide 36 combinations to prevent an incorrect module from being inserted; they do not change the electronic function.
The DIN-rail latch secures the MTU and provides its grounding connection. Field terminals accept solid conductors from 0.2 to 4 mm² or stranded conductors from 0.2 to 2.5 mm², with 7 mm stripped length and 0.5–0.6 N·m tightening torque. The unit has IP20 protection and requires a non-condensing environment; the stated operating range is 0 to +55 °C, while approvals apply from +5 to +55 °C.
TU835V1 3BSE013236R1 Original Technical Excerpt
Original ABB data-sheet pages cover the exact article, field connections, module compatibility and electrical limits. PDF · 2 pages.TU835V1 3BSE013236R1 Installation & Verification Guide
Apter Power field guide covering power-group separation, mechanical keys, field terminals and ModuleBus checks. PDF · 5 pages.
Application scope: Use the unit for single S800 I/O termination arrangements. Conversion accuracy, ranges and channel diagnostics belong to the selected I/O module and must be checked separately.
Fused transducer supply
Bring each sensor power connection through its fused terminal while keeping the associated signal connection identifiable.Separated power groups
Organize two isolated process-supply groups without bridging their returns through unintended field wiring.Single analog I/O stations
Connect compatible AI810, AI815 or AI845 modules through a mechanically keyed field-wiring base.Station maintenance
Preserve field-terminal assignment while checking the fitted module, rail grounding and ModuleBus continuity.
Identify both supply groups and isolate them before disturbing field terminals.
Set both mechanical keys for the intended module before inserting it; never force a mismatch.
Check channel loading and the 8 A process-connection limit separately.
Use the specified conductor range, 7 mm strip length and 0.5–0.6 N·m torque.
Confirm mechanical engagement and the intended DIN-rail grounding path.
Provide suitable enclosure protection for IP20 equipment and prevent condensation.
Alternative Names
Technical notes
Power distribution: Evaluate the two isolated groups, 2 A channel limit and 8 A process-connection limit together.
Module relationship: Mechanical keys and ModuleBus position signals establish the intended module location; input accuracy is determined by the fitted I/O module.
Technical reference: ABB TU835V1 Data Sheet, article 3BSE013236R1.
FAQ View All FAQ
-
How do the two supply groups in TU835V1 3BSE013236R1 help separate field circuits?The process voltage can feed two individually isolated groups. Preserve that separation in the external power and return wiring; an unintended bridge defeats the intended grouping.
-
Can every channel on TU835V1 3BSE013236R1 draw 2 A through one process connection?No. The 2 A limit applies per I/O channel, while the maximum current through a process connection is 8 A. Evaluate the shared connection loading as well as each channel.
-
Does changing the keys on TU835V1 3BSE013236R1 change the input measurement function?No. The two six-position keys provide mechanical coding only. They prevent an unsuitable module from being inserted and do not alter the MTU or I/O-module electronics.
-
Which analog modules can use TU835V1 3BSE013236R1 in a single-I/O station?AI810, AI815 and AI845 can use this MTU in single-I/O arrangements. Their measurement functions and configured ranges remain properties of the selected I/O module.
-
How does TU835V1 3BSE013236R1 establish its I/O module position on ModuleBus?It passes ModuleBus to the module and the next MTU, shifting the outgoing position signals so that the installed module receives the correct position address.
-
What conductor preparation is required at the terminals of TU835V1 3BSE013236R1?Use 0.2–4 mm² solid or 0.2–2.5 mm² stranded conductors. Strip 7 mm and tighten the connection to 0.5–0.6 N·m, keeping loose strands clear of adjacent terminals.
-
Why must the DIN-rail latch on TU835V1 3BSE013236R1 be fully engaged?The latch locks the MTU to the standard DIN rail and supports the grounding connection. Check both secure engagement and the cabinet grounding arrangement before energization.
-
Can TU835V1 3BSE013236R1 operate in a condensing cabinet?No. The humidity range is 5–95% RH without condensation, and protection is IP20. Use an enclosure and environmental controls appropriate to those limits.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.