505-4732

32-Point DC Output Module
In Stock
Ships by Monday, October 26
Fast Shipping Available

Product Describe:

Siemens 505-4732 is a double-wide SIMATIC 505 module with 32 non-latching DC outputs for 6 to 24 V DC loads.

Ask our team:

Get a quick price for: 505-4732
Quantity*
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy.

Technical specifications for 505-4732

Technical specifications for 505-4732

  • Manufacturer:
    Siemens
  • Product Category:
    PLC Systems
  • Spare Part Number:
    505-4732
  • Estimated shipping dimensions:
    4.1x18.6x26.6cm
  • Weight:
    0.6 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    Germany
  • Output channels:
    32
  • Rated load supply:
    6 to 24 V DC
  • Operating range:
    4.5 to 34 V DC
  • Minimum load:
    5 mA
  • Overload:
    5 A for 1 ms
  • ON-state drop:
    2.0 V
  • OFF-state leakage:
    0.2 mA
  • Protection:
    Diode kickback; reverse-voltage protection to 34 V DC
  • Output behavior:
    Non-latching, unprotected
  • Module format:
    Double-wide

Information

Information

Overview Manuals Common Applications Product Precautions
Siemens 505-4732 provides thirty-two DC output points in a double-wide SIMATIC 505 module format.
  • Provides 32 DC output channels.
  • Supports a 6 to 24 V DC rated load supply.
  • Uses diode kickback protection for inductive switching.
  • Occupies a double-wide rack position.

The 32-point dc output module belongs to the SIMATIC 505 modular control platform. Selection must preserve the documented signal role, terminal arrangement and rack interface.

Important Notice: Verify the complete Siemens 505-4732 marking, terminal assignment, rack position and configured signal behavior before replacement.

Siemens 505-4732 Manuals & Downloads
Siemens 505-4732 Technical Reference (PDF)Siemens 505-4732 Installation & Commissioning Guide (PDF)

The Technical Reference covers the product function, system role and technical selection. The installation guide covers identification, connection checks, commissioning and the acceptance record.

High-density DC actuation
Switch 32 approved DC field loads from the controller rack.
Relay-panel control
Drive interposing relays and indicator circuits within the load limits.
Machine output mapping
Preserve an established 32-point output allocation during maintenance.
Legacy SIMATIC 505 support
Restore the double-wide output role without changing the process logic.
Before installing Siemens 505-4732, confirm the documented system, interfaces and controlled configuration.
1
Reserve the complete double-wide rack position before installation.
2
Isolate rack power and every external DC load supply.
3
Label output, common and supply conductors before removal.
4
Confirm load current, group current and inrush stay within the approved design.
5
Retain appropriate suppression at inductive field devices.
6
Inspect both module and terminal-block connectors before engagement.
7
Verify polarity and common grouping before applying field power.
8
Exercise each output and confirm the intended load and interlock response.

Technical notes

Technical notes

Verify the complete Siemens 505-4732 marking, terminal assignment, rack position and configured signal behavior before replacement.

FAQS

  • How many outputs are provided by Siemens 505-4732?
    The module provides 32 DC outputs.
  • How much rack space does Siemens 505-4732 require?
    It uses a double-wide SIMATIC 505 module position.
  • Which DC supply is rated for Siemens 505-4732?
    The rated load supply is 6 to 24 V DC, with a documented operating range of 4.5 to 34 V DC.
  • What minimum load applies to Siemens 505-4732?
    The minimum load is 5 mA.
  • How does Siemens 505-4732 protect inductive loads?
    The outputs include diode kickback protection; retain approved suppression at the field device.
  • Are Siemens 505-4732 outputs latching?
    No. The outputs are non-latching.
  • What must be reviewed before energizing Siemens 505-4732?
    Review polarity, commons, load and group current, inrush and the double-wide rack position.
  • Which test confirms Siemens 505-4732 operation?
    Command all assigned points and verify the corresponding loads and safety interlocks.
Trusted by 5,000+ plants worldwide | Backed by our vast inventory of top-tier control parts, modules and cards, fast shipments are dispatched to cover your urgent needs. ABOUT US >>
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer`s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Product Browsing History

We’re Here When You Need Us

From product insights to customer service needs, our experienced service team will focus on getting you what you need quickly

Enquire

Complete our online form.

Call Us

Speak to one of our team.

Live Chat

Send us a message.