F3330

8-Channel Safety-Related Digital Output Module
In Stock
Ships by Wednesday, October 14
Fast Shipping Available

Product Describe:

HIMA F3330 is an eight-channel safety-related digital output module with integrated safety shutdown and automatic output testing. Its manufacturer sheet specifies resistive or inductive loads up to 500 mA / 12 W per channel and direct lamp loads up to 4 W.

Ask our team:

Get a quick price for: F3330
Quantity*
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy.

Technical specifications for F3330

Technical specifications for F3330

  • Manufacturer:
    HIMA
  • Product Category:
    PLC Systems
  • Spare Part Number:
    F3330
  • Estimated shipping dimensions:
    2x19x12.8cm
  • Weight:
    0.14 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Output channels:
    8
  • Output current:
    Up to 500 mA per channel
  • Resistive or inductive load:
    Up to 12 W
  • Direct lamp load:
    Up to 4 W
  • Internal voltage drop:
    Maximum 2 V at 500 mA
  • Line resistance:
    Maximum 11 ohm, outward and return
  • Undervoltage trip:
    At 16 V or below
  • Output leakage:
    Maximum 350 microampere
  • Test pulse duration:
    Maximum 200 microseconds
  • Space requirement:
    4 TE

Information

Information

Overview Manuals Common Applications Product Precautions
HIMA F3330 is an eight-channel safety-related digital output module with integrated safety shutdown and automatic output testing. Its manufacturer sheet specifies resistive or inductive loads up to 500 mA / 12 W per channel and direct lamp loads up to 4 W.
  • Eight safety-related digital output channels are documented for F3330.
  • Resistive or inductive loads are specified up to 500 mA / 12 W per output.
  • Direct lamp connection is specified up to 4 W.
  • Automatic output readback and walking-bit tests support diagnostics.

Use this module within the approved HIMA rack, field-wiring and safety-logic design.

Important Notice: Confirm the full F3330 marking, Z 7138 / 3330 plug, L- supply and every connected load before replacement.

HIMA F3330 Manuals & Downloads
HIMA F3330 Technical Reference (PDF)HIMA F3330 Installation & Commissioning Guide (PDF)

The first PDF gives F3330 output values and manufacturer-documented interfaces; the second is a separate connection and acceptance checklist. Both use the original HIMA F 3330 (9912) data sheets as their technical basis.

Safety output switching
Use the documented safety-related outputs in an approved HIMA control system.
Resistive load control
Switch a resistive load within the F3330 500 mA / 12 W channel limit.
Inductive load control
Use the specified diode protection for an approved inductive field load.
Lamp indication
Drive a permitted lamp circuit within the direct 4 W limit.
For HIMA F3330, verify the exact output wiring, load limits and approved cabinet safety design before changing a module.
1
Record the complete F3330 marking and installed revision.
2
Apply the site-approved isolation procedure before disturbing the card.
3
Verify all eight output-channel assignments at the front plug.
4
Confirm each resistive or inductive load remains within 500 mA / 12 W.
5
Keep direct lamp circuits within the documented 4 W limit.
6
Check the required diode arrangement for inductive loads.
7
Verify L- supply and the documented loss-of-supply response.
8
Record controlled output readback, safety shutdown and release approval.

Technical notes

Technical notes

Use the exact F3330 marking and approved HIMA cabinet documentation when verifying load type, Z 7138 / 3330 plug variant, L- supply, output testing and safe-isolation response. Do not assume another F333x card is interchangeable.

FAQS

  • What is HIMA F3330?
    It is an eight-channel safety-related digital output module.
  • What load can each output switch?
    The original HIMA sheet specifies up to 500 mA / 12 W for a resistive or inductive load.
  • What is the direct lamp limit?
    The manufacturer lists direct lamp connection up to 4 W.
  • How does the module check its outputs?
    It uses output-signal readback and automatic switching/crosstalk walking-bit testing.
  • What must be verified before replacement?
    Confirm the full F3330 marking, exact front-plug variant, field load, L- supply and approved safety logic.
Trusted by 5,000+ plants worldwide | Backed by our vast inventory of top-tier control parts, modules and cards, fast shipments are dispatched to cover your urgent needs. ABOUT US >>
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer`s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Product Browsing History

We’re Here When You Need Us

From product insights to customer service needs, our experienced service team will focus on getting you what you need quickly

Enquire

Complete our online form.

Call Us

Speak to one of our team.

Live Chat

Send us a message.