The A1072 execution contributes a two-second postpurge and supports the documented LHL-LF and HF proven functions. External subbase, timer and flame-sensing choices remain part of the burner design rather than properties supplied by the relay module alone.
Commissioning should prove each permissive transition in order, observe ignition timing and verify that loss-of-flame and lockout responses match the approved cause-and-effect record.
Important Notice: Check the selected pilot flame-establishing period and purge-timer setting against the burner sequence before the module is returned to automatic operation.
Important Notice: The Technical Reference identifies the A1072 electrical and sequence characteristics; the Installation & Commissioning Guide separates wiring, timing and burner-safety checks into a controlled workflow.